【摘要】:目前国内不同区域的几台660 MW机组陆续发生发电机程跳逆功率保护拒动事故。通过对保护装置的动作逻辑及计算原理进行分析,结合现场运行的实际情况对拒动装置进行校验,发现保护装置在功率平面上的实际动作曲线与理想动作曲线有较大偏差。根据逆功率保护算法原理分析该偏差来自功率因数角的采样误差,由此面向装置生产厂家给出了功率因数角的优化计算方法。同时针对采用程跳逆功率保护的用户提出了在无功水平很低时进行打闸操作的最优运行策略。
[Abstract]:At present, several 660- MW units in different regions of our country have occurred the failure accident of generator range hopping power protection one after another. Based on the analysis of the logic and calculation principle of the protection device, combined with the actual situation of the field operation, it is found that the actual action curve of the protection device in the power plane has a large deviation from the ideal action curve. According to the principle of inverse power protection algorithm, the sampling error from power factor angle is analyzed, and the optimal calculation method of power factor angle is presented for the equipment manufacturer. At the same time, the optimal operation strategy is put forward for the users who adopt range hopping inverse power protection when the reactive power level is very low.
【作者单位】: 华能陕西渭南热电有限公司;河南机电职业学院;西安热工研究院有限公司;
【基金】:秦岭发电厂科技协会基金资助
【分类号】:TM621.3

【相似文献】

相关期刊论文 前10条

1 孙惟东;逆功率保护的运行问题及其对策[J];华东电力;1992年08期

2 赵民,侯佳才,张成武;电压互感器二次回路异常引起发电机逆功率保护误动作的原因分析及解决方法[J];黑龙江电力;2005年04期

3 张爱斌;戴日俊;刘玉龙;武侠;张军;;发电机程序逆功率保护回路改造[J];内蒙古电力技术;2005年06期

4 丁锡文;尚雄英;;600MW机组逆功率保护拒动原因及对策[J];安徽电力;2010年02期

5 申爱兵,赵民,成艳霞;发电机逆功率保护误动作的分析及解决[J];东北电力技术;2003年09期

6 管新娟;朱忠亭;李东岭;;发电机正向低功率及逆功率保护配置及整定[J];电力系统保护与控制;2011年04期

7 陈伟;孟洪汉;张志强;孙幸光;;600MW核电机组的逆功率保护[J];科技视界;2013年34期

8 冯亮;;电厂逆功率保护停机的改进[J];华电技术;2008年05期

9 王海彬;;索拉机组发电机逆功率保护与发动机熄火保护停机研究[J];中国石油和化工标准与质量;2012年06期

10 蔡红升,崔艳玲;集成电路发电机逆功率保护特点及存在问题[J];华中电力;1998年06期