一种矿用无功补偿装置并联电容器组保护方法
发布时间:2018-07-09 15:37
本文选题:矿山电网 + 无功补偿装置 ; 参考:《工矿自动化》2017年07期
【摘要】:针对现有矿用无功补偿装置并联电容器组保护方法存在的成本高、灵敏性差、保护整定计算复杂等问题,分析了矿用低压无功补偿装置并联电容器组发生故障时的电容电流分布特性及故障特征;根据故障时会出现三相不平衡对地电容电流导致零序电流不为零,且非故障电容器组零序电流与故障电容器组零序电流不相等的结论,提出了一种以零序电流为判据的无功补偿装置并联电容器组保护方法,仿真结果验证了该方法的有效性和可行性。
[Abstract]:In view of the problems of high cost, poor sensitivity and complex calculation of protection setting, the existing protection methods for mine reactive power compensator shunt capacitor banks have many problems, such as high cost, poor sensitivity and complex calculation. The characteristics of capacitor current distribution and fault characteristics of shunt capacitor banks in mine low voltage reactive power compensator are analyzed, according to the three phase unbalanced earth capacitance current, the zero sequence current is not zero. And the conclusion that zero sequence current of non fault capacitor bank is not equal to zero sequence current of fault capacitor bank is not equal, a shunt capacitor bank protection method of reactive power compensator based on zero sequence current is proposed. Simulation results show that the method is effective and feasible.
【作者单位】: 山东科技大学电气与自动化工程学院;
【基金】:山东省自然科学基金资助项目(ZR2016EEM13)
【分类号】:TD605
【相似文献】
相关期刊论文 前3条
1 易五毛;;谐波对并联电容器组的影响及其对策[J];化学工程与装备;2009年08期
2 郝服明;无功补偿并联电容器组的放电问题[J];甘肃工业大学学报;1986年01期
3 ;[J];;年期
相关会议论文 前10条
1 冉启鹏;陈欣;董伟;;半封闭式并联电容器组事故频发的原因[A];2011年云南电力技术论坛论文集(入选部分)[C];2011年
2 朱小军;;变电站并联电容器组串抗率分析[A];重庆市电机工程学会2010年学术会议论文集[C];2010年
3 杨益芹;李兴唐;;并联电容器组在工厂中的安装位置和容量[A];二○○二电力电容器学会论文集[C];2002年
4 吴琼;;集合式并联电容器组运行中常见的故障[A];2004年电力电容器学会论文集[C];2004年
5 王欣;;变电站并联电容器组故障分析及整治方案[A];2011年云南电力技术论坛论文集(入选部分)[C];2011年
6 刘w,
本文编号:2109834