不同供水工况毛细管网地板辐射供暖实验研究
发布时间:2018-05-01 16:02
本文选题:毛细管网 + 辐射供暖 ; 参考:《湖南大学学报(自然科学版)》2017年11期
【摘要】:针对夏热冬冷地区冬季供暖问题,以空气源热泵+毛细管网地板辐射供暖系统为对象建立实验系统.实验测试并分析了供水温度分别为40℃,37℃,35℃,33℃和30℃时,不同供水工况毛细管网地板辐射供暖房间的室内空气温度、各内壁面温度的变化特性以及室内环境的舒适性.实验结果表明:在重庆地区,当毛细管网辐射面积占地面的50%,毛细管网间距为20mm,填充层厚度为50mm的豆石混凝土,面层为12mm的木质地板时,40℃,37℃,35℃,33℃和30℃供水工况稳定时的室内温度分别为18.73℃,18.06℃,17.03℃,16.09℃和15.28℃;室内热感觉(PMV)分别为-0.65,-0.82,-1.09,-1.31和-1.44;不满意百分率(PPD)分别为14%,19.08%,30.18%,40.71%和47.39%;各工况室内竖直方向和水平方向上最大温差分别为0.39℃和1.12℃.该地区供水温度≥33℃时,室内温度可满足舒适要求;供水温度≥37℃时,室内PMV和PPD满足我国热舒适评价标准,各工况毛细管网地板辐射供暖系统室内温度分布非常均匀.
[Abstract]:In order to solve the problem of heating in hot summer and cold winter, an experimental system was established with air source heat pump capillary net floor radiant heating system as the object. The indoor air temperature, inner wall surface temperature and indoor environment comfort of capillary net floor radiant heating room under different water supply conditions were tested and analyzed when the water supply temperature was 40 鈩,
本文编号:1830068
本文链接:https://www.wllwen.com/jianzhugongchenglunwen/1830068.html