当前位置:主页 > 科技论文 > 建筑工程论文 >

多热源联合热泵的性能模拟

发布时间:2018-05-10 20:34

  本文选题:燃气内燃机热泵 + 烟气余热利用 ; 参考:《天津大学学报(自然科学与工程技术版)》2017年02期


【摘要】:基于燃气内燃机热泵较高的烟气余热利用价值,提出了一种利用内燃机烟气与太阳能联合驱动的氨水吸收式热泵循环,建立了传统的燃气内燃机压缩式热泵与吸收式热泵的联合供能系统模型,并通过模拟计算分析了系统性能系数的影响,并与传统燃气热泵的热力性能进行了对比.结果表明,该系统在不增加能耗的基础上,一次能源利用率从原来的1.49提高到1.98,输出热量从86,k W增加到115,k W,同时烟气余热回收率从0.20提高到0.29.
[Abstract]:Based on the high utilization value of flue gas waste heat in gas combustion engine heat pump, a ammonia water absorption heat pump cycle driven by internal combustion engine flue gas and solar energy is proposed. The combined energy supply system model of traditional compressing heat pump with gas combustion engine and absorption heat pump is established, and the influence of system performance coefficient is analyzed through simulation calculation, and the thermodynamic performance of traditional gas heat pump is compared with that of traditional gas heat pump. The results show that the primary energy efficiency is increased from 1.49 to 1.98, the output heat is increased from 86 kW to 115 kW, and the recovery rate of flue gas residual heat is increased from 0.20 to 0.29 on the basis of no increase in energy consumption.
【作者单位】: 天津大学机械工程学院;
【基金】:国家自然科学基金资助项目(51076111,51276124) 教育部高等学校博士学科点专项科研基金资助项目(20130032130006)~~
【分类号】:TU83

【相似文献】

相关期刊论文 前5条

1 卢智利;大型建筑中应用应急柴油发电机实现冷热电三联供及其实例分析[J];能源研究与信息;2001年01期

2 邱林;;燃气机热泵系统不同联供运行模式一次能源利用率的分析[J];暖通空调;2006年06期

3 蒋爽;端木琳;李震;舒海文;;海水空调—空调节能环保新技术[J];建筑热能通风空调;2006年04期

4 苏磊;张红;;住宅小区天然气热电冷联产方案性能分析[J];天然气工业;2005年11期

5 ;[J];;年期

相关会议论文 前2条

1 刘传乾;;几种空调形式的一次能源利用率分析[A];2008铁路暖通空调学术年会论文集[C];2008年

2 吴集迎;;沼气机热泵系统的节能分析[A];2007年福建省暖通空调制冷学术年会论文资料集[C];2007年

相关硕士学位论文 前1条

1 陈强;热电一体机的设计及其热流分析[D];上海工程技术大学;2016年



本文编号:1870781