直驱永磁风力发电机绕组短路保护研究
本文关键词: 直驱永磁发电机 绕组短路计算 ANSOFT暂态仿真 主保护配置 出处:《新疆大学》2017年硕士论文 论文类型:学位论文
【摘要】:随着风力发电机组装机容量的增大和投产运营数量的增多,风电产业得到了迅速发展,风电在中国的能源中占比越来越大。最近时期以来,因风力发电机内部小故障,导致大面积机组被切除,最终造成电网电压跌落,引起严重事故。风力发电机绕组短路是机组内部典型的故障之一,电机的绕组短路故障能够产生危害性极大的电流,这将间接或直接地给电网带来巨大的经济损失,因此十分有必要对风力发电机内部绕组配置主保护。风电机组内部绕组保护研究可以提高风力发电场的运行效率,降低风电机组故障的发生,有效地提高机组运行的安全性,甚至对能源结构的调整以及风电产业的发展都具有十分重大的作用。首先,论文概述了直驱永磁同步风力发电机的绕组结构以及三相静止坐标系下永磁发电机的数学模型,建立了直驱永磁风力发电机空载有限元模型。在此模型基础上用外电路模拟匝间及单相接地短路,基于ANSOFT MAXWELL暂态仿真得到故障前后绕组电流的波形并分析其特征,根据定子绕组短路电流的大小,找出其故障规律。其次,分析了永磁发电机不同匝数绕组短路故障,以1.5MW直驱永磁风力发电机绕组为研究对象,利用ANSOFT MEXWELL仿真得出短路电流有效值,得出当定子发生匝间短路时,定子各相电流呈不对称分布,且随着故障程度的加深,故障相电流的增幅及幅值明显大于非故障相。第三,对发电机绕组单相接地短路故障进行了仿真,对比分析得出故障前后电流变化趋势,深入研究绕组的短路特征,得出绕组发生单相接地短路故障时,各相短路电流对发电机绕组的威胁更加严重。最后,针对直驱永磁风力大电机组绕组发生绕组匝间及单相接地故障,配置了“一纵两横”的绕组短路保护,从而改变了直驱永磁风力发电机组无保护的现状。通过内部绕组不同故障程度的数据对比分析,对于匝间短路故障,各相横向短路电流差明显大于纵向短路电流差,横差保护的灵敏度优于不完全纵差保护的灵敏度。
[Abstract]:With the increase of installed capacity and operational quantity of wind turbine, wind power industry has developed rapidly, and wind power accounts for more and more energy in China. Because of the small fault inside the wind turbine, the large area unit is excised, and finally the voltage of the power network falls, which causes the serious accident. The wind turbine winding short circuit is one of the typical faults inside the unit. The winding short circuit fault of the motor can produce great harmful current, which will bring huge economic loss to the power network indirectly or directly. Therefore, it is necessary to configure the main protection for the windings of the wind turbine. The research on the protection of the inner windings of the wind turbine can improve the operational efficiency of the wind farm and reduce the occurrence of the fault of the wind turbine. Effectively improve the safety of unit operation, even the adjustment of energy structure and the development of wind power industry have a very important role. First of all. The winding structure of direct-drive permanent magnet synchronous wind generator and the mathematical model of permanent magnet generator in three-phase static coordinate system are summarized in this paper. The no-load finite element model of direct-drive permanent magnet wind turbine is established, and the inter-turn and single-phase earthing short circuit is simulated by external circuit on the basis of the model. Based on the transient simulation of ANSOFT MAXWELL, the waveform of winding current before and after the fault is obtained and its characteristics are analyzed. According to the size of short-circuit current of stator winding, the fault law is found out. Secondly. The short-circuit fault of different turns winding of permanent magnet generator is analyzed. Taking the winding of 1.5MW direct-drive permanent magnet wind generator as the research object, the effective value of short-circuit current is obtained by ANSOFT MEXWELL simulation. It is concluded that when inter-turn short circuit occurs in the stator, the stator phase currents show asymmetric distribution, and with the deepening of the fault degree, the increase and amplitude of the fault phase current is obviously larger than that of the non-fault phase. Third. The single-phase earthing short-circuit fault of generator windings is simulated, and the trend of current change before and after fault is obtained, and the short-circuit characteristics of windings are deeply studied, and the single-phase earthing short-circuit fault of windings is obtained. The short-circuit current of each phase is more serious to the generator winding. Finally, in view of the winding inter-turn and single-phase grounding fault of the direct drive permanent magnet wind motor group windings, the "one longitudinal and two horizontal" winding short circuit protection is provided. Thus, the situation of direct-drive permanent magnet wind turbine without protection is changed. By comparing and analyzing the data of different fault degree of internal windings, the inter-turn short-circuit fault is analyzed. The transverse short-circuit current difference of each phase is obviously larger than that of longitudinal short-circuit current, and the sensitivity of transverse differential protection is better than that of incomplete longitudinal differential protection.
【学位授予单位】:新疆大学
【学位级别】:硕士
【学位授予年份】:2017
【分类号】:TM315
【参考文献】
相关期刊论文 前10条
1 李磊;景春阳;黄晓芳;;直驱式永磁风力发电机综合保护算法的研究[J];风能;2014年03期
2 胡维超;;定子绕组相间短路与接地故障分析及处理[J];防爆电机;2013年03期
3 胡兆网;王宏华;;基于PSCAD的双馈风力发电系统低电压穿越仿真研究[J];机械制造与自动化;2012年02期
4 王飞;郑日红;段建东;;基于双馈机组风电场并入网后的自适应保护[J];电机与控制应用;2012年03期
5 张保会;王进;李光辉;郝治国;刘志远;薄志谦;;具有低电压穿越能力的风电接入电力系统继电保护的配合[J];电力自动化设备;2012年03期
6 栗然;高起山;刘伟;;直驱永磁同步风电机组的三相短路故障特性[J];电网技术;2011年10期
7 李斌;王琦;隆贤林;;风电场接入系统继电保护的配置与整定[J];吉林电力;2011年04期
8 张敬;李颖晖;朱喜华;;基于Maxwell 2D的同步发电机定子绕组匝间短路故障研究[J];微电机;2010年11期
9 雷晓梅;;变速变桨距风力发电机组控制方法研究[J];甘肃科技;2010年02期
10 刘春志;黄政;孔维敏;;一起水轮发电机横差保护动作的检查及分析[J];水电站机电技术;2009年06期
相关会议论文 前1条
1 宁世国;叶林;;永磁同步发电机建模与运行特性研究[A];纪念中国农业工程学会成立30周年暨中国农业工程学会2009年学术年会(CSAE 2009)论文集[C];2009年
相关博士学位论文 前1条
1 张德;风能资源数值模拟及其在中国风能资源评估中的应用研究[D];兰州大学;2009年
相关硕士学位论文 前10条
1 项丹;永磁直驱风力发电机组全功率变流器控制策略的研究[D];重庆大学;2013年
2 吕靖峰;我国风能产业发展及政策研究[D];中央民族大学;2013年
3 左岩松;大型直驱式永磁风力发电系统故障退磁仿真分析[D];华中科技大学;2013年
4 申瑞鹏;中日新能源产业发展模式比较研究[D];上海师范大学;2013年
5 梁宇;大规模风电场并网运行的故障分析及保护策略研究[D];华中科技大学;2013年
6 严嘉鸿;基于盘式无铁心永磁同步发电机的海流能发电系统研究[D];天津大学;2012年
7 刘彬;无速度传感器的直驱永磁风力发电变流器控制研究[D];哈尔滨工业大学;2012年
8 薛小倩;风速模拟与风力机风轮模拟的研究[D];内蒙古科技大学;2012年
9 曲庭余;双馈风力发电机高电压穿越技术研究[D];合肥工业大学;2012年
10 刘守刚;110kV智能变电站设计及其可靠性分析[D];华北电力大学;2012年
,本文编号:1446314