直驱风机变流控制系统对次同步频率分量的响应机理研究
发布时间:2018-01-26 14:59
本文关键词: 次同步振荡 永磁直驱风机 网侧变流控制系统 锁相环 d/q解耦控制环节 出处:《电网技术》2017年06期 论文类型:期刊论文
【摘要】:在概述变流控制系统锁相环和d/q解耦控制环节传递函数的基础上,采用小信号方法,依次推出当控制系统各环节馈入1个次同步频率分量时输出信号的解析表达式,讨论信号经变流控制系统后频率变化关系,对比分析多个输出次/超同步频率信号的相对幅值关系。进一步以时域仿真及我国某新能源汇集地区PMU(phasor measurement unit)实测数据,分别验证理论分析的正确性。同时根据理论分析,对永磁直驱风机汇集母线存在多个次/超同步频率分量的现象给出解释,也对抑制主要次/超同步频率分量提供依据。
[Abstract]:On the basis of summarizing the phase locked loop and D / Q decoupling control link transfer function of the variable current control system, the small signal method is adopted. The analytical expression of the output signal is derived when one sub-synchronous frequency component is fed into each link of the control system, and the frequency variation relationship after the signal is controlled by the variable current control system is discussed. The relative amplitudes of multiple output sub-/ supersonic frequency signals are compared and analyzed. Further, time domain simulation and PMU (. Phasor measurement unit. According to the theoretical analysis, the phenomenon that there are several frequency components of supersynchronous frequency in the bus of permanent magnet direct drive fan is explained. It also provides the basis for suppressing the primary / supersonic frequency components.
【作者单位】: 新能源电力系统国家重点实验室(华北电力大学);国家电力调度控制中心;
【基金】:国家自然科学基金项目(51627811) 高等学校学科创新引智计划项目(B08013) 国家电网公司科技项目(SGXJ0000KXJS1500669)~~
【分类号】:TM614
【正文快照】: 释,也对抑制主要次/超同步频率分量提供依据。0引言2015年7月1日,国内某新能源汇集地区永磁直驱风电场发生次同步振荡,在风电汇集线上监测到19.4、29.6、39.8、60.2、70.4、80.6、90.8 Hz等多个次同步及超同步频率分量,导致直流送端附近3台660 MW机组因轴系扭振跳机,西北电网,
本文编号:1465901
本文链接:https://www.wllwen.com/kejilunwen/dianlidianqilunwen/1465901.html