基于相位特性的高压输电线路双端非同步故障测距算法
发布时间:2018-01-21 13:37
本文关键词: 双端不同步数据 故障测距 伪根 高压输电线路 出处:《电力系统自动化》2015年22期 论文类型:期刊论文
【摘要】:现有的大部分双端数据不同步测距算法由于伪根的存在可能导致测距失败。针对这一不足,基于线路分布参数模型,利用电压正序分量与负序分量的比值或者电压正序分量与故障正序分量的比值消除不同步角,并利用相位的单调性进而推出一种双端非同步故障测距算法。该算法不存在伪根,可以利用二分区间求根法或者弦截求根法快速求取故障距离。EMTP仿真结果表明,该算法测距精度不受过渡电阻、故障类型以及不同步角的影响,计算量小,测距精度高。
[Abstract]:Due to the existence of pseudo-roots, most of the existing two-terminal data asynchronous ranging algorithms may lead to ranging failure. In order to solve this problem, this paper based on the line distribution parameter model. The ratio of the positive sequence component to the negative sequence component or the ratio of the voltage positive sequence component to the fault positive sequence component is used to eliminate the asynchronous angle. By using the monotonicity of phase, a two-terminal asynchronous fault location algorithm is proposed, which does not have pseudo-roots. The fault distance. EMTP simulation results show that the accuracy of the algorithm is not affected by the transition resistance, fault type and synchronization angle. Small amount of calculation and high ranging accuracy.
【作者单位】: 华北电力大学电气与电子工程学院;国网冀北电力有限公司检修分公司;
【基金】:中央高校基本科研业务费专项资金资助项目(2014xs74)~~
【分类号】:TM75
【正文快照】: 0引言输电线路故障后,迅速准确的故障测距不仅对及时修复线路和保证可靠供电,而且对电力系统的安全稳定和经济运行都有十分重要的作用[1]。故障测距算法可分为行波测距[2-5]和故障分析法测距[6-9]。行波原理的测距存在波头识别、有测距死区和投资比较大等缺点,故故障分析法原
【参考文献】
相关期刊论文 前10条
1 束洪春,高峰,陈学允,,许承斌;双端不同步采样的高压输电线路故障测距算法研究[J];电工技术学报;1997年06期
2 全玉生,王晓蓉,杨敏中,严璋,李晓兵,于峥,康林贤,司鲁东,佟科,刘晓峰;工频双端故障测距算法的鲁棒性问题和新算法研究[J];电力系统自动化;2000年10期
3 滕林,刘万顺,李营,李贵存,秦红霞;一种实用的新型高压输电线路故障双端测距精确算法[J];电力系统自动化;2001年18期
4 梁远升;王钢;李海锋;;双端不同步线路参数自适应时频域故障测距算法[J];电力系统自动化;2009年04期
5 陈羽;刘东;徐丙垠;;基于广域网络信息的行波测距算法[J];电力系统自动化;2011年11期
6 牛敏,赵舫;一种改进的双端测距算法[J];电力系统及其自动化学报;1998年01期
7 束洪春,司大军,葛耀中,陈学允;利用双端不同步数据的高压输电线路故障测距实用算法及其实现[J];电网技术;2000年02期
8 梁军,麻常辉,