XLPE电缆终端绝缘气隙缺陷的局部放电烧蚀特征
发布时间:2018-05-07 16:01
本文选题:电缆终端 + 气隙缺陷 ; 参考:《绝缘材料》2014年06期
【摘要】:为研究气隙缺陷导致交联聚乙烯(XLPE)电缆终端绝缘破坏的机理,对内部设置气隙缺陷的XLPE电缆终端进行电热老化实验与局部放电(PD)检测实验,并通过扫描电镜(SEM)和能谱仪(EDS)分析老化前后气隙的表面形态及元素组成。结果表明:XLPE电缆终端绝缘内部的气隙缺陷在运行条件下PD迅速发展并表现出显著的阶段性特征,气隙通道的快速击穿与气隙接触点周围的气孔受电场应力作用而扩张的关系密切,接触点经放电烧蚀逐渐形成碳颗粒。
[Abstract]:In order to study the mechanism of air gap defect leading to the insulation failure of XLPE cable terminal, the XLPE cable terminal with air gap defect was tested by electrothermal aging test and partial discharge (PD) test. The surface morphology and elemental composition of air gap before and after aging were analyzed by scanning electron microscopy (SEM) and energy dispersive spectrometer (EDS). The results show that the air gap defect in the terminal insulation of the cable terminal of: XLPE develops rapidly under the operating conditions and shows remarkable stage characteristics. The rapid breakdown of the air gap channel is closely related to the expansion of the pores around the air gap contact point by electric field stress. The contact point is gradually ablated by discharge to form carbon particles.
【作者单位】: 四川大学电气信息学院;四川电力科学研究院;
【基金】:国网四川省电力公司科技项目(12H0596) 国网重庆市电力公司科技项目(12H0933)
【分类号】:TM855
【参考文献】
相关期刊论文 前8条
1 王超;刘毅刚;刘刚;张尧;;有限元法应用于电缆终端应力锥缺陷分析[J];高电压技术;2007年05期
2 姜芸;闵虹;夏荣;李文杰;;高压交联电缆接头局部放电的电容耦合法检测及分析[J];高电压技术;2010年08期
3 刘刚;陈志娟;;10kV交联聚乙烯电缆终端主绝缘含空气气隙缺陷试验[J];高电压技术;2012年03期
4 游世宇;吴雨波;万利;周凯;李旭涛;;高压大电流下电缆附件电热老化实验装置的研制[J];高压电器;2013年07期
5 刘曦;陶霰韬;周凯;杨琳;赵威;;XLPE电缆绝缘修复技术中缆芯导体的腐蚀性评估[J];绝缘材料;2013年01期
6 周凯;李旭涛;黄华勇;魏长明;杨可;;电缆终端安装刀痕缺陷的局部放电特性分析[J];电力系统保护与控制;2013年10期
7 常文治;李成榕;苏,