一起酒店会议室CO中毒事件调查
发布时间:2018-05-24 06:58
本文选题:会议室 + CO ; 参考:《环境与健康杂志》2017年10期
【摘要】:为了解重庆市某酒店会议室CO中毒事件发生经过及原因,采用流行病学和卫生学调查、实验室检测等进行分析,结果显示,20名患者的临床症状均符合CO中毒表现,现场监测发现CO浓度超标,会议室锅炉排烟管道上穿,且空调无新风系统。提示该事件为急性CO中毒,建议调查中尽可能做实验室诊断,并加强公共场所排烟管道的合理布局。
[Abstract]:In order to understand the occurrence and causes of CO poisoning in a hotel conference room in Chongqing, epidemiological and hygienic investigation and laboratory tests were used to analyze the results. The results showed that the clinical symptoms of 20 patients were in accordance with the symptoms of CO poisoning. Field monitoring found that CO concentration exceeded the standard, the exhaust pipe of conference room boiler was pierced, and the air conditioning had no fresh air system. It is suggested that laboratory diagnosis should be made as far as possible in the investigation, and the rational layout of smoke pipes in public places should be strengthened.