反渗透系统压差高的原因分析及解决措施
本文选题:反渗透 + 保安过滤器 ; 参考:《水处理技术》2017年09期
【摘要】:反渗透系统在运行过程中反复出现系统压差迅速上升的问题,通过拆解膜组件对其进行研究并利用扫描电镜及能谱仪检测,原因确定为超滤水箱出口的硫酸盐还原菌等厌氧菌滋长使得保安过滤器及反渗透系统受到细菌污染,从而导致反渗透系统压差上升较快。针对该现象提出了定期对反渗透系统进行酸碱清洗并灭菌的方法,主要是对超滤水箱出口的系统(主要是管道)进行杀菌处理和对保安过滤器进行离线和在线双重杀菌处理。
[Abstract]:During the operation of the reverse osmosis system, the pressure difference of the system increases rapidly repeatedly. The membrane assembly is disassembled and detected by scanning electron microscope (SEM) and energy dispersive spectrometer (EDS). The reason is that the anaerobic bacteria such as sulfate reducing bacteria at the outlet of the ultrafiltration tank make the safety filter and reverse osmosis system polluted by bacteria which results in the pressure difference of reverse osmosis system rising rapidly. Aiming at this phenomenon, a method of periodically cleaning and sterilizing the reverse osmosis system is put forward, which is mainly to sterilize the system at the outlet of the ultrafiltration tank (mainly the pipeline) and the off-line and on-line double sterilization of the security filter.
【作者单位】: 浙江浙能绍兴滨海热电有限责任公司;杭州水处理技术研究开发中心有限公司;西安热工研究院有限公司;国网宁夏电力公司宁夏电力科学研究院;
【分类号】:TQ028.8
【相似文献】
相关期刊论文 前10条
1 胡振华;;二级反渗透系统的性能方程式[J];水处理技术;1993年02期
2 许建平,刘旭;反渗透系统的清洗[J];工业水处理;2004年10期
3 董翠玲;郭强;;反渗透系统的控制方法[J];天津科技;2012年03期
4 刘魁元;在田纳西河流域固体燃料电厂缩小反渗透系统投资和维护[J];工业水处理;2000年04期
5 马倩;;海德能8040膜与4040膜在反渗透系统中的应用比较[J];绿色科技;2010年10期
6 林庆峰;俞威;狄小伟;王炜;;反渗透系统的设计与应用[J];工业水处理;2008年04期
7 赵鑫;田小康;杨广瑞;;反渗透系统高有机复合污染诊断、处理及防治[J];清洗世界;2011年08期
8 陈红英;;反渗透系统故障分析[J];科技风;2009年14期
9 司利平;反渗透系统的运行参数控制与事故处理[J];膜科学与技术;2000年04期
10 杨昆,郭嘉,王宇彤;反渗透系统的性能变化分析及量化评价方法[J];膜科学与技术;2005年05期
相关会议论文 前3条
1 高松松;;反渗透系统的运行维护[A];2013年全国冶金节水与废水利用技术研讨会文集[C];2013年
2 张炜;;加碱在反渗透系统中的应用[A];2008中国水处理技术研讨会暨第28届年会论文集[C];2008年
3 丁伟;;反渗透系统的给水预处理有关技术问题探讨[A];中国石油和石化工程研究会第八届年会文集[C];2004年
,本文编号:1983920
本文链接:https://www.wllwen.com/guanlilunwen/gongchengguanli/1983920.html