特高压直流输电系统新型谐波抑制方法研究
发布时间:2018-03-11 21:05
本文选题:新型换流变压器 切入点:特高压直流输电 出处:《湖南大学学报(自然科学版)》2016年10期 论文类型:期刊论文
【摘要】:传统的特高压直流输电系统一般在换流站交流网侧布置滤波兼无功补偿装置.为了避免谐波对换流变压器的不良影响,本文提出了一种滤波绕组并联的感应滤波换流变压器的谐波抑制方法,文中描述了其接线方案,解释了其滤波机理,并与传统的滤波方案进行了对比分析.以酒泉-湖南的±800kV特高压直流输电的工程参数为依据,搭建了所提滤波方案和传统方案的仿真模型.两个模型的阀侧和网侧电流的对比分析证明,新型谐波抑制方法效果良好.
[Abstract]:The traditional UHV HVDC transmission systems generally arrange filtering and reactive power compensation devices on the AC network side of the converter station. In order to avoid the adverse effects of harmonics on converter transformers, In this paper, a method of harmonic suppression of induction filter converter transformer with parallel filter windings is proposed. The connection scheme is described, and the filtering mechanism is explained. And compared with the traditional filtering scheme, based on the engineering parameters of 卤800kV UHVDC transmission in Jiuquan-Hunan province, The simulation models of the proposed filtering scheme and the traditional scheme are built. The comparison and analysis between the valve side and the grid side of the two models show that the new harmonic suppression method is effective.
【作者单位】: 国家电能变换与控制工程技术研究中心(湖南大学);国网北京经济技术研究院;国网湖南省电力公司检修公司;
【基金】:特高压直流接入750kV交流电网无功平衡和谐波抑制技术研究(14430101001322)
【分类号】:TM721.1;TM714.3
【相似文献】
相关期刊论文 前10条
1 ;天威保变第三台换流变压器一次试验成功[J];变压器;2009年01期
2 张杰;罗隆福;张志文;李勇;李季;赵志宇;;新型换流变压器建模及故障计算[J];高电压技术;2009年12期
3 李溪;;大型换流变压器的移位方法[J];沿海企业与科技;2012年10期
4 文,
本文编号:1599890
本文链接:https://www.wllwen.com/kejilunwen/dianlidianqilunwen/1599890.html