35kV直挂式角接链式STATCOM控制策略
发布时间:2019-02-15 12:27
【摘要】:在大型电弧炉的补偿应用中,为了应对电网电压不对称的应用条件,提出一种35 k V直挂式角接链式STATCOM网侧电流闭环综合补偿控制策略。该策略将经典电纳平衡补偿和网侧电流闭环控制相结合,使得链式STATCOM装置可以在电网电压不对称条件下对电弧炉负载进行无功、谐波和负序的综合补偿。经35 k V/±40 MVA STATCOM装置实际运行,结果表明:STATCOM装置能够在保持快速的动态响应的同时,实现良好的稳态补偿效果,并能抵御电网电压不平衡造成的影响。
[Abstract]:In the application of large electric arc furnace compensation, in order to deal with the application condition of voltage asymmetry in power network, a 35 kV direct mounted angle link STATCOM current closed loop compensation control strategy is proposed. This strategy combines the classical compensation with the closed loop control of the grid side current, which makes the chain STATCOM device can compensate the electric arc furnace load with reactive power, harmonic and negative sequence under the condition of the asymmetry of the grid voltage. The actual operation of the 35kV / 卤40 MVA STATCOM device shows that the STATCOM device can maintain fast dynamic response and achieve a good steady-state compensation effect, and can resist the influence caused by the unbalanced voltage of the power network.
【作者单位】: 北京交通大学电气工程学院;清华大学电机工程与应用电子技术系;北京四方继保自动化股份有限公司;
【分类号】:TM761
[Abstract]:In the application of large electric arc furnace compensation, in order to deal with the application condition of voltage asymmetry in power network, a 35 kV direct mounted angle link STATCOM current closed loop compensation control strategy is proposed. This strategy combines the classical compensation with the closed loop control of the grid side current, which makes the chain STATCOM device can compensate the electric arc furnace load with reactive power, harmonic and negative sequence under the condition of the asymmetry of the grid voltage. The actual operation of the 35kV / 卤40 MVA STATCOM device shows that the STATCOM device can maintain fast dynamic response and achieve a good steady-state compensation effect, and can resist the influence caused by the unbalanced voltage of the power network.
【作者单位】: 北京交通大学电气工程学院;清华大学电机工程与应用电子技术系;北京四方继保自动化股份有限公司;
【分类号】:TM761
【参考文献】
相关期刊论文 前1条
1 谢化安;王辉;梁晓军;;500kV东莞变电站±200MVA静止同步补偿器的控制功能试验对比研究[J];高电压技术;2013年03期
【共引文献】
相关期刊论文 前9条
1 高明振;何刚;胡广振;张永康;姜齐荣;李旷;;100MVA级静止同步补偿器的可靠性分析[J];高电压技术;2013年07期
2 齐文超;郭俊杰;杨振华;;几种35kV变电站设计方案优化的分析[J];电源技术应用;2013年11期
3 赵成勇;李丹;刘羽超;郭春义;许韦华;阳岳希;;含有STATCOM的高压直流输电系统控制方法[J];高电压技术;2014年08期
4 郭郓闻;张建设;胡云;韩伟强;廖梦君;;大容量分布式STATCOM对南方电网交直流系统影响的实时仿真研究[J];高电压技术;2014年08期
5 刘锦宁;刘洋;何伟斌;;±200M var静止同步补偿器的电网电压控制策略[J];电力自动化设备;2015年05期
6 季振东;孙毅超;李东野;赵剑锋;黄允凯;;星形和三角形连接的链式H桥STATCOM不平衡补偿分析[J];高电压技术;2015年07期
7 苏华锋;;35kV±200 MVA STATCOM暂态响应分析[J];高电压技术;2015年10期
8 刘锦宁;刘洋;何伟斌;;±200 MVA STATCOM装置直流电压控制策略优化[J];高电压技术;2015年10期
9 郑传材;劳志p,