新型逆流式露点间接蒸发冷却器性能研究
发布时间:2018-02-08 14:53
本文关键词: 蒸发冷却 逆流 露点温度 板翅式换热器 出处:《低温与超导》2017年05期 论文类型:期刊论文
【摘要】:提出了一种新型的逆流式露点间接蒸发冷却器,研究了进气的相对湿度、温度变化对其冷却(湿球)效率的影响。结果显示:相对湿度和温度的变化对冷却器的冷却(湿球)效率具有显著的影响,较低的相对湿度和温度能获得较高的冷却(湿球)效率,所有运行条件下的冷却(湿球)效率超过100%。当环境温度为303.15K,相对湿度为10%时,冷却器的效率最高为128.5%,表明冷却器具有较好的降温效果;改进后的结构相比较原始结构,进口压力降低1.107%,产气温度降低了0.314K。
[Abstract]:A new type of countercurrent indirect dew point evaporative cooler is proposed, and the relative humidity of inlet air is studied. The results show that the change of relative humidity and temperature has a significant effect on the cooling efficiency of the cooler. Lower relative humidity and temperature can achieve higher cooling (wet bulb) efficiency, and under all operating conditions the cooling (wet bulb) efficiency is more than 100. When the ambient temperature is 303.15K, the relative humidity is 10. The highest efficiency of the cooler is 128.5, which indicates that the cooler has a better cooling effect, and the improved structure reduces the inlet pressure by 1.107and the gas production temperature by 0.314Kcompared with the original structure.
【作者单位】: 郑州轻工业学院能源与动力工程学院;机械工业第六设计研究院有限公司;
【基金】:国家自然科学基金资助项目(51476148) 河南省杰出青年基金项目(154100510014) 河南省教育厅创新团队项目(17IRTSTHN029)资助
【分类号】:TB657
【相似文献】
相关期刊论文 前2条
1 李天保;;逆流式斜波填料冷却塔简化热力计算[J];化工与通用机械;1982年10期
2 ;[J];;年期
相关会议论文 前2条
1 何瑞贤;;逆流式与横流式冷却水塔特性比较[A];第三届海峡两岸制冷空调学术技术交流会暨冰蓄冷技术研讨会论文专辑[C];1997年
2 陈君红;陈沛霖;;逆流式封闭冷却塔数学模型的建立、求解及实验验证[A];全国暖通空调制冷1998年学术文集[C];1998年
,本文编号:1495703
本文链接:https://www.wllwen.com/guanlilunwen/gongchengguanli/1495703.html