毛细管空调与传统空调的空气调节性能的对比试验
发布时间:2018-07-29 11:54
【摘要】:以能源与动力工程实验中心节能减排实验室为背景,对毛细管空调系统与传统空调进行制冷及除湿性能对比实验。监测室内温湿度分布情况;结果显示:毛细管辐射空调运行时,在人体主要活动范围内温度平均在25.5~27.3℃,相对湿度在56.8%~65.0%;对比毛细管辐射空调运行时,传统空调温度分布均匀性较差,温度在25.0~26.3℃之间,垂直方向上随着高度升高逐渐降低,水平方向上各测点的温度分布不均。这种温度分布使得人体有忽冷忽热的感觉,各测点相对湿度波动较明显,但是垂直和水平方向的相对湿度值相差在5%以内,较毛细管辐射空调供冷相对湿度区间较小。
[Abstract]:Based on the energy conservation and emission reduction laboratory of the experimental center of energy and power engineering, a comparative experiment on the refrigeration and dehumidification performance of capillary air conditioning system and traditional air conditioning system was carried out. Monitoring indoor temperature and humidity distribution, the results show that the average temperature in the main range of human body activity is 25.5N 27.3 鈩,
本文编号:2152601
[Abstract]:Based on the energy conservation and emission reduction laboratory of the experimental center of energy and power engineering, a comparative experiment on the refrigeration and dehumidification performance of capillary air conditioning system and traditional air conditioning system was carried out. Monitoring indoor temperature and humidity distribution, the results show that the average temperature in the main range of human body activity is 25.5N 27.3 鈩,
本文编号:2152601
本文链接:https://www.wllwen.com/jingjilunwen/jianzhujingjilunwen/2152601.html