【摘要】:为分析室内步行街排烟方案的排烟效果,文章采用CFD方法对3、8 MW火灾功率下的16个排烟工况进行数值模拟,结果表明:在相同条件下,中庭顶部采用机械排烟方式比自然排烟方式排烟效果更好;在中庭回廊设置排烟有助于将商铺火灾溢出的烟气及时排除;中庭采用机械排烟方式时,中庭顶部排烟口布置方式对排烟效果影响不大,而采用自然排烟方式时,中庭顶部排烟口按天窗方式布置比按高侧窗方式布置排烟效果更好。
[Abstract]:In order to analyze the smoke exhaust effect of indoor pedestrian street smoke exhaust scheme, the CFD method is used to simulate 16 smoke exhaust conditions under 3, 8 MW fire power. The results show that under the same conditions, the mechanical smoke exhaust mode at the top of the atrium is better than the natural smoke exhaust mode, and the smoke exhaust in the atrium corridor is helpful to remove the smoke spilled from the shop fire in time. When the mechanical smoke exhaust mode is adopted in the atrium, the arrangement of the smoke outlet at the top of the atrium has little effect on the smoke exhaust effect, but when the natural smoke exhaust mode is adopted, the smoke exhaust port at the top of the atrium is better than the high side window.
【作者单位】: 安徽省合肥市公安消防支队;中国科学技术大学火灾科学国家重点实验室;
【分类号】:TU892

【参考文献】

相关期刊论文 前4条

1 杨焱;路世昌;智会强;张晋;;中庭烟气流动规律及防排烟系统的研究[J];安全;2006年05期

2 杨林;王彬彬;蒋勇;;基于数值模拟的室内商业街火灾烟气输运研究[J];中国安全生产科学技术;2008年04期

3 刘明非;王泽宇;张国昊;雷波;袁中原;李颖臻;;回廊式超高中庭排烟探讨[J];制冷与空调(四川);2013年01期

4 徐茜;;商场中庭底部设置溜冰场的自然排烟有效性分析[J];消防技术与产品信息;2013年11期

【共引文献】

相关期刊论文 前8条

1 张立龙;朱杰;卢小翠;;机械排烟系统优化设计数值模拟研究[J];中国安全生产科学技术;2010年01期

2 季经纬;武爽;赵平;张敬瑶;;大型超市火灾情况下人员疏散模拟分析[J];中国安全生产科学技术;2011年10期

3 张娟;朱国庆;张磊;李欢欢;;有风条件下剧院火灾自然排烟效果分析[J];中国安全生产科学技术;2011年11期

4 周志望;周妍静;王浩波;;大空间建筑不同排烟系统作用下的烟气控制效果研究[J];火灾科学;2014年03期

5 杨p芊,

本文编号:2514540


资料下载
论文发表

本文链接:https://www.wllwen.com/kejilunwen/anquangongcheng/2514540.html


Copyright(c)文论论文网All Rights Reserved | 网站地图 |

版权申明:资料由用户5d42a***提供,本站仅收录摘要或目录,作者需要删除请E-mail邮箱bigeng88@qq.com