杜童水电站进水口水头损失试验研究
发布时间:2018-01-16 00:18
本文关键词:杜童水电站进水口水头损失试验研究 出处:《水电能源科学》2016年02期 论文类型:期刊论文
【摘要】:针对杜童水电站进水口水头损失过大导致电站出力不足的问题,基于重力相似准则,建立了1∶50的试验模型,分别对不同墩头形状和不同前室长度进行了模型试验。结果表明,尖圆型墩头的水头损失较原矩形修圆墩头平均降低了8.63%,说明尖圆型墩头能更好地平稳水流,但水头损失依然过大;将水电站前室部分延长20m后,与未延长前相比,水头损失平均降低了47.57%,说明该水电站原设计为减小工程量,过分缩短了前室长度,导致水头损失过大,为类似工程提供了借鉴。
[Abstract]:Based on gravity similarity criterion , a 1 : 50 test model is established for the problem of insufficient power output due to excessive water head loss in Dutong Hydropower Station . The results show that the water head loss of the toe circular pier head is reduced by 8.63 % than that of the original rectangular pier head . The average loss of water head is reduced by 47.57 % compared with that of the original rectangular pier head . The original design of the hydropower station is reduced by 47.57 % , which indicates that the original design of the hydropower station is reduced , which leads to excessive water loss and provides reference for similar projects .
【作者单位】: 河北农业大学城乡建设学院;河北省水利技术试验推广中心;河北省水利水电第二勘测设计研究院;
【分类号】:TV732.1;TV135
【正文快照】: 1工程概况杜童水电站位于鹿泉市境内,是一座季节性发电的径流式电站,电站总装机容量N为3×1 250kW,总设计流量Q总为75.33 m3/s,单机机组设计水头6.4m,设计流量Q设为25.11m3/s,采用轴伸贯流式水轮发电机组;设计年发电量为645×104kW·h,主要供给鹿泉市生产生活用电。该电站前池
【相似文献】
相关期刊论文 前10条
1 袁晓伟;王博;;管道突扩处水头损失系数实验研究[J];青海大学学报(自然科学版);2009年03期
2 叶飞;高学平;贾秋影;郎晓艳;;输水管系弯曲管路的水头损失研究[J];中国给水排水;2011年07期
3 娄晓凤;高芬;;聚氯乙烯管道水头损失的简便计算[J];黑龙江水利科技;2012年01期
4 董淑芳,何同溪;曼宁公式在管道水头损失计算中适用性的讨论[J];山东建筑工程学院学报;1998年01期
5 张小康;杨建东;;水头损失的CFD计算[J];中国农村水利水电;2009年05期
6 陈明;;引水式电站引水水头损失分析[J];科技风;2010年09期
7 宋贤良,夏海峰,周秀彩,蒋丽君,李彦军;浮箱式水力自动门水头损失系数试验研究[J];扬州大学学报(自然科学版);2003年02期
8 杜涛;刘焕芳;金瑾;李强;韩义超;;多孔流体分布管出流及水头变化规律研究[J];节水灌溉;2014年02期
9 孙小利;王建跃;Allen Thompson;;用环形断面管流模拟多年生植物的人工湿地的水头损失[J];水利学报;2011年08期
10 张忠辉;林德金;付斌;李金锁;;斐济南德瑞瓦图水电站工程输水系统水头损失计算探讨[J];水利水电工程设计;2010年03期
,本文编号:1430718
本文链接:https://www.wllwen.com/kejilunwen/shuiwenshuili/1430718.html